1. 1. 1. 1. 1. Standard:
GB/T 5023-2008 / IEC 60227-1997 JB/T 8734-2016
2. Application:
For electric devices, instruments, telecom equipment, power lighting lines etc. with AC rated voltage of 450/750V and below or DC 1000V and below.
3. Operating Performance:
1). a. Rated voltage U0/U is 450/750V & 300/500V. The system nominal voltage should not be higher than 1.5 times of rated voltage of cable.
b. Attention: the system operating voltage is allowed to be higher than system nominal voltage continuously by 10%. If the cable rated voltage is not lower than the system nominal voltage, the cable can be used under the operating voltage higher than the rated voltage by 10%.
2). Minimum Bending Radius for fixed wiring(D: outer diameter of cable)
4D (D≤25mm);
6D( D>25mm).
3). The temperature for cable laying should not be under 0℃.
4. Type & Model:
Type | Model |
60227 IEC 05 (BV) | 70℃ Singel Copper Core Non-sheathed Cable for Internal Wiring |
BV | PVC Insulated Copper Core Cable |
60227 IEC 01 (BV) | Single Core Rigid Conductor Non-sheathed Cable |
BVVB | Flat PVC Insulated & PVC Sheath Cable |